
| NO. | Model | Control Output | Alarm |
| 1 | TM_-SB10 | SSR | 1 |
| 2 | TM_-RB10 | RELAY | 1 |
| Sample rate | 2 times/per second |
| Relay capacity | AC 250V /3A Life of rated load>100,000 times |
| Power supply | AC/DC 100 ~ 240V (85-265V) |
| Power consumption | < 6VA |
| Environment | Temperature of indoor:0 ~ 50 no condensation,Humidity:<85%RH,altitude<2000m |
| Storage enenvironment | -10 ~ 60, no condensation |
| SSR output | DC 24V pulse voltage,load<30mA |
| Insulation impedance | Input, output, power VS meter cover >20MΩ |
| ESD | IEC/EN61000-4-2 Contact ±4KV /Air ±8KV perf.Criteria B |
| Pulse traip anti-interference | IEC/EN61000-4-4 ±2KV perf.Criteria B |
| Surge immunity | IEC/EN61000-4-5 ±2KV perf.Criteria B |
| Voltage drop & short interruption immunity | IEC/EN61000-4-29 0% ~ 70% perf.Criteria B |
| Dielectric strength | Signal input /output /power 1500VAC 1min,between lower than 60V circuits, DC500V,1min |
| Total weight | About 400g |
| Shell material | The shell and panel frame PC/ABS (Flame Class UL94V-0) |
| Panel material | PET(F150/F200) |
| Power failure memory | 10 years,times of writing: 1 million times |
| Safety Standard | IEC61010-1 Overvoltage category ,pollution level 2,level(Enhanced insulation) |
| Input type | Measure range | Resolution | Accuracy | Input impedance/auxiliary current |
| K | -50 ~ 999 | 1°C | 0.5%F.S±3digits | >500kΩ |
| J | 0 ~ 999 | 1°C | 0.5%F.S±3digits | >500kΩ |
| E | 0 ~ 850 | 1°C | 0.5%F.S±3digits | >500kΩ |
| T | -50 ~ 400 | 1°C | 0.5%F.S±2 | >500kΩ |
| PT100 | -200 ~ 600 | 1°C | 0.5%F.S±3digits | 0.2mA |
| CU50 | -50 ~ 150 | 1°C | 0.5%F.S±3 | 0.2mA |
| CU100 | -50 ~ 150 | 1°C | 0.5%F.S±1 | 0.2mA |