GL200 series IO system is a Liancheng blade IO system, with a wide range of modules, including 16/32 channel digital input module (source + drain) and 16/32 channel digital output module (source / drain); 4/8 channel analog input module (voltage + current), 4/8 channel analog output module (voltage/current), resolution up to 16 bits; Temperature measurement module (RTD/thermocouple) with 24-bit resolution.
Small, convenient, fast, distributed product design is the trend of future automation development, blade IO module, with a very small shape design, greatly reduce the size of the control system, easy to install, stable and reliable, widely used in all walks of life of industrial control, while bringing convenience to customers, with microsecond channel signal acquisition cycle, to solve the real-time signal detection and feedback on the field side, and timely response to system decision-making. The high-resolution design provides reliable real-world data in the field for the system algorithms.
Product Model | GL200-DI module | GL200-DQ module | GL200-AI module |
Module Type: | Digital input module | Digital output module | Analog input module |
Number of Channels: | 16/32 | 16/32 | 4/8 channel voltage/current inputs |
Contact Type: | Transistor, source/drain | Transistor (source/drain type), relay type | ±10V、±5V、0~10V、0~5V |
ON/OFF response time: | 0.5ms | 0.5ms | 4~20mA、0~20mA |
Isolation method: | Optoelectronic isolation, isolation withstand voltage 3KVrms | Optoelectronic isolation, isolation withstand voltage 3KVrms | Optoelectronic isolation, isolation withstand voltage 3KVrms |
GL200-AQ module | |
Module Type: | Analog output |
Number of Channels: | 4/8 current/voltage output |
Output Voltage Range: | 0~10V |
Output Current Range: | 4~20mA、0~20mA |
Output Accuracy: | Voltage± 0.1% F.S |
Product Model | GL200-TC module | GL200-RTD module |
Module Type: | Temperature measurement module | Temperature measurement module |
Number of Channels: | 4 | 4 |
Sensor Type: | Thermocouples K, J, E, B, N, R, S, T | RTD PT100, PT1000 |
Resolution: | 24-bit | 24-bit |
Accuracy (25°C at room temperature): | (±0.15%F.S)±2 | <0.1%F.S |
GL200-DQ8S2 module | |
Module Type: | Digital High Current Output Module (Source Type) |
Number of Channels: | 8 |
Channel Current: | 2A |
ON/OFF response time: | 100us |
Output: | Transistor source type |
Product Model | GL200-TC2P module | GL200-RTD2P module |
Module Type: | Temperature control module | Temperature control module |
Number of Channels: | 2 | 2 |
PID Control: | Support PID parameter autotuning | Support PID parameter autotuning |
Sensor Type: | Thermocouples K, J, E, B, N, R, S, T | RTD PT100, PT1000 |
Output Type: | PWM wave output | PWM wave output |
Specifications
GL200 series digital input modules | ||
Product model | GL200-DI16 | |
Order number | 20030102 | |
General | ||
Product iteration | Fifth generation | |
Power supply | Backplane power supply (module power supply) | 5V DC (4.75V DC~5.25V DC) |
Terminal power supply (load power supply) | Not | |
Dimensions (W x H x D) mm | 12*105*85 mm | |
Weight | 73g | |
Operating/storage temperature | -20°C~55°C/-40°C~70°C | |
Relative humidity | 10%~90%RH, no condensation | |
Ingress protection | IP20 | |
Elevation | Below 3000m | |
Certification Information | CE marked | |
Technical parameters | ||
Module type | Digital inputs | |
Number of channels | 16 | |
Channel type | Transistor, source + drain | |
Enter the voltage level | 24V DC (20.4V DC~28.8V DC) | |
Module power consumption | 5VDC/35mA | |
Input Current (Typical) | 4mA | |
Filtering time | / | |
Channel breaking | ON status | >15V |
OFF status | 12V | |
Hardware response time | ON | 100us |
OFF | 100us | |
Isolation method | Each channel is opto-isolated | |
Diagnostic LEDs | 1x Run, 1x Fault, 16x Channel Indication | |
Overload protection | / | |
Hot-swappable | In the tank | |
Software parameters | ||
Channel logic level configuration | Not supported | |
Independent channel enable configuration | Not supported | |
Configure the diagnostic escalation function | In the tank | |
Shutdown mode | Input refresh is supported | |
I/O refresh mode | Free-running refresh (keep synchronous refresh) | |
IO mapping | Bit-by-bit access and byte-by-byte access are supported |
GL200 series digital output module | ||||
Product model | GL200-DQ16D | GL200-DQ16S | GL200-DQ8S2 | |
Order number | 20030208 | 20030205 | 20030212 | |
General | ||||
Product iteration | Fifth generation | Fifth generation | Fifth generation | |
Power supply | Backplane power supply (module power supply) | 5V DC (4.75V DC~5.25V DC) | 5V DC (4.75V DC~5.25V DC) | 5V DC (4.75V DC~5.25V DC) |
Terminal power supply (load power supply) | 24V DC (20.4V DC~28.8V DC) | 24V DC (20.4V DC~28.8V DC) | 24V DC (20.4V DC~28.8V DC) | |
Dimensions (W x H x D) mm | 12 *105 *85 mm | 12 *105 *85 mm | 12 *105 *85 mm | |
Weight | 74g | 74g | 73g | |
Operating/storage temperature | -20°C~55°C/-40°C~70°C | -20°C~55°C/-40°C~70°C | -20°C~55°C/-40°C~70°C | |
Relative humidity | 10%~90%RH, no condensation | 10%~90%RH, no condensation | 10%~90%RH, no condensation | |
Ingress protection | IP20 | IP20 | IP20 | |
Elevation | Below 3000m | Below 3000m | Below 3000m | |
Certification Information | CE marked | CE marked | CE marked | |
Technical parameters | ||||
Module type | Digital output | Digital output | Digital output | |
Number of channels | 16 | 16 | 8 | |
Channel type | Transistor, drain type | Source | Source | |
Input Current (Typical) | 10mA | 10mA | 10mA | |
Module power consumption | 5VDC/70mA | 5VDC/70mA | 5VDC/70mA | |
Filtering time | / | / | / | |
Voltage output range | 24V DC ±10% (21.6V DC ~26.4V DC) | 24V DC ±10% (21.6V DC ~26.4V DC) | 24V DC ±10% (21.6V DC ~26.4V DC) | |
Load current | 0.5A/point, 4A/module | 0.5A/point, 4A/module | 2A/point, 16A/module | |
Hardware response time | ON | 100us | 100us | 100us |
OFF | 100us | 100us | 100us | |
Isolation method | Each channel is opto-isolated, and the isolation withstand voltage 3KVrms | |||
Diagnostic LEDs | 1x Run, 1x Fault, 16x Channel Indication | 1x Run, 1x Fault, 16x Channel Indication | 1x Run, 1x Fault, 8x Channel Indication | |
Overload protection | In the tank | In the tank | In the tank | |
24V power supply anti-reverse connection | In the tank | In the tank | In the tank | |
Hot-swappable | In the tank | In the tank | In the tank | |
Software parameters | ||||
Channel logic level configuration | Not supported | Not supported | Not supported | |
Independent channel enable configuration | Not supported | Not supported | Not supported | |
Configure the diagnostic escalation function | In the tank | In the tank | In the tank | |
Shutdown mode | Press to stop the output mode and the preset value output, no longer refresh | |||
Stop the output mode | There are three ways to hold, clear, and preset the output | |||
IO mapping | Bit-by-bit access and byte-by-byte access are supported |
GL200 series analog input module | GL200 series analog output module | ||||
Product model | GL200-AI4 | GL200-AI8 | GL200-AQ4 | GL200-AQ8 | |
Order number | 20030416 | 20030417 | 20030518 | 20030519 | |
General | |||||
Product iteration | Fifth generation | Fifth generation | Fifth generation | Fifth generation | |
Power supply | Backplane power supply (module power supply) | 5V DC (4.75V DC~5.25V DC) | 5V DC (4.75V DC~5.25V DC) | 5V DC (4.75V DC~5.25V DC) | 5V DC (4.75V DC~5.25V DC) |
Terminal power supply (load power supply) | 24V DC (20.4V DC~28.8V DC) | 24V DC (20.4V DC~28.8V DC) | 24V DC (20.4V DC~28.8V DC) | 24V DC (20.4V DC~28.8V DC) | |
Dimensions (W x H x D) mm | 12 *105 *85 mm | 12 *105 *85 mm | 12 *105 *85 mm | 12 *105 *85 mm | |
Weight | 72g | 75g | 74g | 75g | |
Operating/storage temperature | -20°C~55°C/-40°C~70°C | -20°C~55°C/-40°C~70°C | -20°C~55°C/-40°C~70°C | -20°C~55°C/-40°C~70°C | |
Relative humidity | 10%~90%RH, no condensation | 10%~90%RH, no condensation | 10%~90%RH, no condensation | 10%~90%RH, no condensation | |
Ingress protection | IP20 | IP20 | IP20 | IP20 | |
Elevation | Below 3000m | Below 3000m | Below 3000m | Below 3000m | |
Certification Information | CE marked | CE marked | CE marked | CE marked | |
Technical parameters | |||||
Module type | Analog inputs | Analog inputs | Analog output | Analog output | |
Number of channels | 4 | 8 | 4 | 8 | |
Resolution | 16-bit | 24-bit | 16-bit | 16-bit | |
Voltage input | Range | 0~5V,0~10V,±10V,±5V | 0~5V,0~10V,±10V,±5V | 0~5V,0V~10V,±10V,±5V | 0~5V,0V~10V,±10V,±5V |
Impedance | 110KΩ | 110KΩ | 1KΩ | 1KΩ | |
Accuracy (25°C) | <0.1%F.S | <0.1%F.S | <0.1%F.S | <0.1%F.S | |
Limit | ±11V | ±11V | ±10V | ±10V | |
Current input | Range | 0~20mA,4~20mA,-20~20mA | 0~20mA,4~20mA,-20~20mA | 0~20mA,4~20mA | 0~20mA,4~20mA |
Impedance | 250Ω | 250Ω | 0Ω-1kΩ | 0Ω-1kΩ | |
Accuracy (25°C) | <0.1%F.S | <0.1%F.S | <0.1%F.S | <0.1%F.S | |
Limit | 24mA | 24mA | 22mA | 22mA | |
Isolation method | The channel is not isolated, the system side is photoelectically isolated from the field side, and the isolation withstand voltage is 3KVms | ||||
Diagnostic modality | Field-side power supply detection, open circuit detection, and over-range detection | - | |||
Output protection | - | Overtemperature protection, voltage short circuit protection, current open circuit protection | |||
Diagnostic LEDs | Operation, fault, communication indication; signal input indication; Channel range indication | Operation, fault, communication indication; Signal output indication | |||
24V power supply anti-reverse connection | In the tank | In the tank | In the tank | In the tank | |
Hot-swappable | In the tank | In the tank | In the tank | In the tank | |
Software parameters | |||||
Software input filtering time | Yes, the software can be configured 1~255ms (default 10ms) | / | / | ||
Configure the diagnostic escalation function | In the tank | In the tank | In the tank | In the tank | |
Out-of-limit detection | In the tank | In the tank | In the tank | In the tank | |
Peak hold | In the tank | In the tank | In the tank | In the tank | |
Shutdown mode | Keeps the current value and does not refresh again | Keeps the current value and does not refresh again | Output by shutdown mode and preset value, no longer refreshed | ||
IO mapping | Word-by-word access is supported | Word-by-word access is supported | Word-by-word access is supported | Word-by-word access is supported |
GL200 series temperature measurement module | |||
Product model | GL200-RTD4 | GL200-RTD2P | |
Order number | 20030420 | 20030425 | |
General | |||
Product iteration | Fifth generation | Fifth generation | |
Power supply | Backplane power supply (module power supply) | 5V DC (4.75V DC~5.25V DC) | 5V DC (4.75V DC~5.25V DC) |
Terminal power supply (load power supply) | 24V DC (20.4V DC~28.8V DC) | 24V DC (20.4V DC~28.8V DC) | |
Dimensions (W x H x D) mm | 12 *105 *85 mm | 12 *105 *85 mm | |
Weight | 73g | 72g | |
Operating/storage temperature | -20°C~55°C/-40°C~70°C | -20°C~55°C/-40°C~70°C | |
Relative humidity | 10%~90%RH, no condensation | 10%~90%RH, no condensation | |
Ingress protection | IP20 | IP20 | |
Elevation | Below 3000m | Below 3000m | |
Certification Information | CE marked | CE marked | |
Technical parameters | |||
Module type | Temperature measurement module | Temperature measurement module | |
Number of channels | 4 | 2 | |
Resolution | 24 | 24 | |
Displays sensitivity | 0.1°C,0.1°F | 0.1°C,0.1°F | |
Input terminals | 4 RTD inputs | 2 RTD inputs | |
Sensor type | PT100,PT1000 | Pt100,Pt1000 | |
Wiring | Two-wire/three-wire/four-wire | Two-wire/three-wire/four-wire | |
Accuracy (room temperature 25°C) | <0.1%F.S | <0.1%F.S | |
Accuracy (room temperature -20°C~55°C) | <0.3%F.S | <0.3%F.S | |
Isolation method | The I/O terminals are isolated from the power supply, and the channels are not isolated | ||
Diagnostic modality | Overrun detection, disconnection detection | Overrun detection, disconnection detection | |
Diagnostic LEDs | Operation, fault, communication indication; Signal input indication | ||
The 24V power supply is reversed-proof | In the tank | In the tank | |
Hot-swappable | In the tank | ||
Software parameters | |||
Software input filtering time | 1~100s (default 5s) | 1~100s (default 5s) | |
Configure the diagnostic escalation function | In the tank | In the tank | |
Overrun | Output by max/min | Output by max/min | |
Peak hold | In the tank | In the tank | |
PID control | / | Support PID parameter autotuning | |
I/O refresh mode | Asynchronous refresh according to the sampling time, and synchronous refresh by bus cycle is not required | ||
IO mapping | Word-by-word access is supported |
GL200 series temperature control module | |||
Product model | GL200-TC4 | GL200-TC2P | |
Order number | 20030422 | 20030424 | |
General | |||
Product iteration | Fifth generation | Fifth generation | |
Power supply | Backplane power supply (module power supply) | 5V DC(4.75V DC~5.25V DC) | 5V DC(4.75V DC~5.25V DC) |
Terminal power supply (load power supply) | 24VDC(-15%~+20%) | 24VDC(-15%~+20%) | |
Dimensions (W x H x D) mm | 12 *105 *85 mm | 12 *105 *85 mm | |
Weight | 72g | 72g | |
Operating/storage temperature | -20°C~55°C/-40°C~70°C | -20°C~55°C/-40°C~70°C | |
Relative humidity | 10%~90%RH, no condensation | 10%~90%RH, no condensation | |
Ingress protection | IP20 | IP20 | |
Elevation | Below 3000m | Below 3000m | |
Certification Information | CE marked | CE marked | |
Technical parameters | |||
Module type | Temperature measurement module | Temperature control module | |
Number of channels | 4 | 2 | |
Resolution | 24-bit | 24-bit | |
Sensitivity | 0.1°C,0.1°F | 0.1°C,0.1°F | |
Input terminals | 4 thermocouple inputs | 2 thermocouple inputs | |
Sensor type | K,J,E,B,N,R,S,T | K,J,E,B,N,R,S,T | |
Accuracy (room temperature 25°C) | <0.1%F.S | <0.1%F.S | |
Accuracy (room temperature -20°C~55°C) | <0.3%F.S | <0.3%F.S | |
Isolation method | The I/O terminals are isolated from the power supply, and the channels are not isolated | ||
Compensation Method | Internal cold end compensation | Internal cold end compensation | |
Diagnostic modality | Overrun detection, disconnection detection | ||
Diagnostic LEDs | Operation, fault, communication indication; Signal input indication | ||
The 24V power supply is reversed-proof | In the tank | In the tank | |
Hot-swappable | In the tank | In the tank | |
Software parameters | |||
Software input filtering time | 0~100s (default value: 5s) | 0~100s (default value: 5s) | |
Configure the diagnostic escalation function | In the tank | In the tank | |
Out-of-limit detection | In the tank | In the tank | |
Peak hold | In the tank | In the tank | |
PID control | / | Support PID parameter autotuning | |
I/O refresh mode | Asynchronous refresh according to the sampling time, and synchronous refresh by bus cycle is not required | ||
IO mapping | Word-by-word access is supported |
GL200 series special function module | |||
Product iteration | GL200-CSL | GL200-CSW | |
Order number | 20070140 | 20070140 | |
General | |||
Product iteration | Fifth generation | Fifth generation | |
Power supply | Backplane power supply (module power supply) | 5V DC(4.75V DC~5.25V DC) | 5V DC(4.75V DC~5.25V DC) |
Terminal power supply (load power supply) | 24V DC(20.4V DC~28.8V DC) | 24V DC(20.4V DC~28.8V DC) | |
Dimensions (W x H x D) | 40x105x85mm | 40x105x85mm | |
Weight | 165g | 165g | |
Operating/storage temperature | -20°C~70°C/-40°C~85°C | -20°C~70°C/-40°C~85°C | |
Relative humidity | 5%~95%RH, no condensation | 5%~95%RH, no condensation | |
Ingress protection | IP20 | IP20 | |
Elevation | Below 3000m | Below 3000m | |
Certification Information | CE marked | CE marked | |
Technical parameters | |||
Function | Dual CPU redundancy management module, expandable with 16 GL200 series I/O modules | Dual PLC redundant management communication module | |
Communication | Type of communication | Internally private | / |
Number of extension modules | 16. The internal bus and redundant management module can automatically identify the number of expansion modules and the type and number of I/O on the backplane | / | |
Synchronization mode | Input/output synchronization | / | |
Communication rate | 100Mbps | / | |
Bus interface | LAN A | / | Single-mode dual-core SC fiber interface |
LAN B | / | 10/100Mbps Ethernet interface | |
Diagnostic LEDs | Operation, fault, communication indications | Operation, fault, communication indications | |
24V power supply anti-reverse connection | In the tank | In the tank | |
Hot-swappable | In the tank | / |